4
Electrical installation
Important notes
4
Electrical installation
4.1
Important notes
Danger!
Dangerous voltage
All power terminals remain live for at least three minutes after
mains disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
34
Death or severe injuries when touching the power terminals.
Wait for at least three minutes before working on the power
terminals.
Check that all power terminals are deenergised.
Death or severe injuries when the device is touched in the event
of a fault.
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter ≥ 10 mm
2
or PE conductor must be connected twice)