THE INDOOR UNIT INSTALLATION
16
Mounting the anchor nut and
bolt
- Prepare 4 suspension bolts. (Each bolts
length should be same.)
- Measure and mark the position for the Sus-
pension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the suspen-
sion bolts for locking the suspension bolts on
the ceiling.
- Mount the suspension bolts to the anchor-
nuts firmly.
- Secure the hangers onto the Suspension
bolts (adjust level roughly.) using nuts, wash-
ers and spring washers.
- Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
- Adjust a level on the direction of top-bottom
by adjusting supension bolts. Then the unit
will be declined to the bottomside so as to
drain well.
Model (kBtu/h)
18k/24k
36k/42k/48k/60k
Anchor nut
Ceiling
Nut
Washer
Washer
Washer
A
Suspension
Suspension
Suspension
bolts
bolts
bolts
(Unit : mm)
A
B
1018
355
1418
B
Suspension bolt
Suspension
bolts
Spring
washer
Nut
Hangen
Max.
Washer
12mm
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
- The following parts is option.
Hanging Bolt
- W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
CAUTION
!
Tighten the nut and bolt to prevent unit
from falling
• Drill the piping hole on the wall slightly
tilted to the outdoor side by using a
Ø 70 hole-core drill.
Wall
Indoor
Flat washer
for M10
(accessory)
Flat washer
for M10
(accessory)
Nut
(W3/8 or M10)
Outdoor
Slope gradient for
drain Should be
1/50 ~ 1/100