Electrical Installation; Electrical Requirements - Xylem FLOJET FLO 5.0 Manual De Instrucciones

Bomba automatica de diafragma
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32
Wiring must comply with applicable electrical standards and include
a properly sized fuse or circuit breaker. Improper wiring can cause a
fire resulting in injury or death.
CAUTION: Suggested wiring information is given as a reference. For proper
information please reference local wiring codes and specification guidelines.
Wire Size Table
Total Wire Length - feet (meters)
Pump
Voltage
12 VDC
24 VDC

Electrical installation

Electrical Hazard:
WARNING: Make sure that all connections are performed by qualified installation technicians and in
compliance with the regulations in force.
WARNING: Before starting work on the unit, make sure that the unit and the control panel are isolated
from the power supply and cannot be energized.
Installation:
WARNING:
Observe accident prevention regulations in force.
Use suitable equipment and protection.
Always refer to the local and/or national regulations, legislation, and codes in force regarding
the selection of the installation site, plumbing, and power connections.

Electrical requirements:

The local regulations in force overrule specified requirements listed below.
Electrical connection checklist
Check that the following requirements are met:
The electrical leads are protected from high temperature, vibrations, and
collisions.
The current type and voltage of mains connection must correspond to the
specifications on the data plate on the pump.
Electrical Installation
Diagram
WARNING
FIR E HA Z A RD
Model
Volts
R4320343A
24V
R4426343A
24V
R4420343A
24V
R4425509A
24V
R4425511A
24V
R4425512A
24V
R4320143A
12V
R4420143A
12V
R4426143A
12V
R4425503A
12V
R4425505A
12V
R4425506A
12V
0 - 20 ft
(0 - 6 m)
#14 AWG
(2.5 mm
#16 AWG
(1.5 mm
Figure 5.
Amps
6.0 A
10 A Required
6.0 A
10 A Required
6.0 A
10 A Required
6.0 A
10 A Required
6.0 A
10 A Required
6.0 A
10 A Required
12.0 A
15 A Required
12.0 A
15 A Required
12.0 A
15 A Required
12.0 A
15 A Required
12.0 A
15 A Required
12.0 A
15 A Required
20 - 35 ft
(6 - 9 m)
#12 AWG
2
)
(4 mm
#14 AWG
2
)
(2.5 mm
Fuse
35 - 55 ft
(9 - 12 m)
#10 AWG
2
)
(6 mm
#12 AWG
2
)
(4 mm)
2
)
5

Publicidad

Tabla de contenido
loading

Tabla de contenido