Installation
5.2

Assembly Recommendation

Fig. 8
5.3

Electrical connection (Qualified specialist)

WARNING
Risk of electric shock due to incorrect connections!
Electrical connections must always be carried out by
authorised specialists.
Observe VDE and utility company regulations.
Install pumps for swimming pools and their protection
according to DIN VDE 0100-702.
Install a disconnecting device with at least a 3 mm contact
gap per pole to interrupt the power supply.
WARNING
Risk of electric shock due to voltage on the housing!
A built-in or external overload switch which is set correctly
must be installed for pumps with three-phase or A.C. motors
without motor protection. In doing so, observe the values on
the motor name plate.
Protect power supply with a ground fault circuit interrupter,
nominal residual current I
Only use suitable pipe types according to regional
regulations.
22 EN
≤ 30 mA.