Sensor DIP Switch Settings
DIP 6 / 7 / 8
Trigger mode
The trigger mode enables the user to choose which sensing technologies
should be used to initially turn the load on and which technologies are
required to keep it on. The following settings are possible:
Both:
Requires movement recognition by PIR and US
Either:
Requires movement recognition by PIR or US
PIR:
Requires movement recognition by PIR
US:
Requires movement recognition by US
Initial occupancy:
Sensor technology used to turn the load on (PIR, US, Both, Either)
Maintain Occupancy:
Sensor technology used to keep the load on after initial occupancy (PIR, US, Both, Either)
The trigger mode is selected by DIP switches 6, 7 & 8.
COM 1 + COM 2
ON / OFF
TEST
NOT
MODE
USED
MANUAL
1
2
3
4
5
6
7
8
on
NORMAL
AUTO
NOT
TRIGGER MODE
MODE
USED
(IR CM NOT USED)
ON
Initial Occupancy
Trigger mode options n
Option 1 (factory setting)
Both
Option 2
Both
Option 3
PIR
Option 4
US
Option 5
Either
Option 6
US
Option 7
PIR
Option 8
Either
DIM
ON / OFF
TEST
CONST.
MODE
OFF
MANUAL
1
2
3
4
5
6
7
on
NORMAL
AUTO
CONST.
TRIGGER MODE
MODE
ON
(IR CM NOT USED)
ON
DIP
DIP
Maintain Occupancy
6
7
Either
OFF
OFF
Both
OFF
OFF
Either
OFF
ON
Either
OFF
ON
Either
ON
OFF
US
ON
OFF
PIR
ON
ON
Both
ON
ON
- 20 -
Functions – Settings by Potentiometer
Potentiometer e
Light level setting
The chosen response threshold
can be adjusted from approx.
10 – 1000 lux / 1 – 100 fc.
Application Examples
Night-time mode, minimum setting approx. 10 lux / 1 fc
Corridors, foyers
Stairs, escalators, moving walkways
Restrooms, dining areas
Classrooms, sales floors, gymnasiums
Individual offices, conference and meeting rooms
Laboratories, precision work areas
Daylight mode
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
Brightness is measured directly at the sensor.
Potentiometer f
8
Occupancy time delay setting
The occupancy time delay
setting for switching output 1
is adjustable from a minimum
Pulse mode (except DIM)
If the dial is set to
(fully coun-
terclockwise), the unit is in pulse
mode, i.e. the output is switched
'ON' for approx. 2 sec. Afterwards,
DIP
8
the sensor does not respond to
OFF
ON
OFF
IQ mode
ON
Turned fully clockwise: The stay-
'ON' time is self-learning and
OFF
adjusts dynamically to user
ON
OFF
ON
Control dial turned fully clockwise:
Control dial turned fully
MAX daylight mode
counterclockwise:
MIN night-time operation
Light level settings
of 30 seconds to a maximum of
30 minutes.
movement for approx. 8 sec.
For use with a time delay relay.
(Not available with the DIM-24
sensors).
behavior. The optimum time
The shortest time is 5 min.,
cycle is determined by means of
the longest 20 min.
a learning algorithm.
- 21 -
min
1
2
3
4
5
>=6
max