Functions – Settings by Potentiometer
COM2-24
Potentiometer g
Stay-'ON' time for switching output 2 HVAC
Setting 1 min. - 30 min.
• Turned fully clockwise: max
Potentiometer h
Switch-'ON' delay for switching output 2 HVAC
• Setting 0 sec. – 10 min.
Turning the potentiometer to the
• Turned fully clockwise:
"Auto-HVAC mode" setting reduces
the sensitivity of the "Presence"
Auto-HVAC mode
switching output. The contact only
• Turned fully counterclockwise:
closes after surveying the activity
0 sec. (OFF)
of the space and then signaling
DIM-24
Potentiometer m
Stay 'ON' time DIM before 'OFF' option
Provides basic illumination for the
levels back to basic brightness
selected stay-'ON' time after
after the stay-'ON' time (1 min. -
30 min.) has expired or the
occupancy time delay setting has
expired. The basic illumination
daylight level exceeds the selected
light intensity can be set from 10%
level of brightness. The overall
- 60% (with RC 8 in 10% steps) of
time delay of occupancy time
maximum light intensity. As soon
delay and stay on time DIM before
as a person is detected, the sensor
'OFF' is not able to exceed 30
switches either to the specified
minutes. The setting of the
light intensity (constant-lighting
occupancy time delay is prior to
controller 'OFF') or adjusts to the
the stay on time DIM before 'OFF' .
preselected brightness level
The DIM-24 units have two time
(constant-lighting controller 'ON').
delay setting (Occupied Time
When no movement is detected
Delay & Dim Before OFF Delay).
and the occupancy time setting
has elapsed, the sensor dims light
Reach Adjustment
Potentiometer i
Adjusts ultrasonic reach to specific requirements. Reach
can be adjusted by using the RC8 remote control
commissioning tool.
• Turned fully counterclockwise: min
with a high degree of certainty that
multiple persons are present.
The stay-'ON' time remains active.
The switch-'ON' delay is
inactivated.
The "Occupied Time Delay" is the
time delay that retriggers each
time it detects motion and keeps
the light level at the occupant's
selected comfort level so long as
the space is occupied. After no
motion is detected for the
duration of the "Occupied Time
Delay" the light level is dimmed to
the minimum level for the
duration of the "Dim Before OFF
Delay. " The cumulative sum of the
two time delays will never exceed
30 minutes before the lights will
be turned off.
Vertical adjustment
(PIR reach)
- 22 -

Remote Control

Using the remote control,
Note: The pulse mode cannot be
functions can be conveniently
overridden by the remote control.
activated from the floor.
Switch pulse mode 'OFF' manually.
RC 8 Service Remote
Description
The RC 8 service remote (commissioning tool) gives the
installer the ability to set basic functions of the entire line
of Control Pro sensors via remote control. Each valid press
of a button is indicated by a blue LED flash on the sensor.
3
4
6
12
14
15
Functions
1
Reach setting (factory setting: 50 %)
Ultrasonic coverage can be selected from
minimum, 1/3, 2/3, or maximum by pressing
these buttons. Use this setting to increase or
decrease the coverage (detection range) of the
sensor.
2
Basic light level (10%) (factory setting: 30 min.)
Basic light level deactivated
Basic light level for the time shown
Presence Control remote
control unit:
- RC 8 Service Remote
- RC 4 User Remote
Time setting CH 1 -
stay-'ON' time Switching contact 1 (factory setting: 15 min.)
3
Test mode. The test mode has the purpose of
checking for proper working order as well for
testing the detection zone. Irrespective of ambi-
ent light level and movement, the presence de-
tector activates the light to stay 'ON' for approx.
1
8 sec. Test mode has priority over all other set-
tings. All user-selected potentiometer settings
apply in normal mode. Test mode ends automati-
cally after 10 min.
2
IQ mode. Stay-'ON' time is self-learning and ad-
4
justs dynamically to user behaviour. The opti-
mum time is determined by means of a learning
7
algorithm. The shortest time is 5 min., the long-
8
est time 20 min.
Sets the light to stay 'ON' for a time of your own
5
choice. Each press of the button increments the
9
chosen time setting by 1 minute.
The period of time you want the light to stay
6
10
'ON' for after last detecting movement can be
set from between 5 min., 10 min. to 30 min. by
pressing these buttons.
Time setting CH 2 -
11
Stay-'ON' time Switching contact 2 (HVAC)
13
(factory setting: 30 min.)
16
The period of time you want light 'ON' for / to
7
stay 'ON' for after last detecting movement can
17
be set to either 5, 10, or 15 min. by pressing these
buttons.
Time setting CH 2 -
Delay before switching 'ON' (factory setting: 5 min)
Auto-HVAC mode ON/OFF
8
Automatic adjustment of switch-'ON' delay after
persons are present in the detection zone.
No time delay.
9
Time delay 10 min.
10
Light threshold setting (factory setting:
11
The chosen response threshold can be set from
approx. 10 – 1000 lux.
- 23 -
)