Mounting and Conduit Entry

Digital ballast loops
NEC
PELV (Class 2:
USA) only
Alternate
ballast
wiring
entry
Alternate
ballast
wiring
entry
Notes
• Water damages equipment. Mount in a location
where the hub and processors will not get wet.
Mount within 7˚ of true vertical.
• Digital ballast wiring can be Class 1 or Class 2;
always keep Class 1 and Class 2 wiring separate,
and follow all applicable local and national electric
codes.
• A minimum of 12 in (305 mm) unobstructed space is
required in front of and below the hub for ventilation.
6 Quantum
Light Management Hub
TM
Dedicated feed
Line voltage only
Class 1 or
®
Alternate
ballast
wiring
entry
Front View
Ceiling
PELV (Class 2: USA)
wiring only for control
links and Ethernet
connection
Alternate
PELV
(Class 2:
USA) entry
Alternate
PELV
(Class 2:
USA) entry
Alternate
PELV
(Class 2:
USA) entry
• Enclosure: NEMA Type 1, IP-20 protection
#16 U.S. gauge steel
• Weight: 45 pounds (20.4 kg)
• Surface mount only
• For indoor use only
• 32 - 104 ºF (0 - 40 ºC)
• Relative humidity less than 90% non-condensing
Wall
Side View
R