Panel Mounting

Mounting Guidelines
• For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
• Panel generates heat. Mount only where ambient
temperature is 32-104 °F (0-40 °C).
• Relative humidity must be < 90% non-condensing.
• Reinforce wall structure for panel weight and local
codes; see table.
• Allow 12 in. (305 mm) clearance above and below
panel.
• Mount within 7° of true vertical.
• Mount panel where audible noise is acceptable.
(Internal relays click.)
• Mount panel so line (mains) voltage wiring is at least
6 ft. (1.8 m) from audio or electronic equipment and
associated wiring.
• Install in accordance with all national and local
electrical codes.
Front View
Load circuit wiring
Air flow
Low-
voltage
control
1
wiring for
2
TVM loads
3
4
Do not
obstruct
5
vents!
6
7
8
PELV
(Class 2: USA)
A
B
C
Wiring
N
Feed wiring
LP8/32-1204ML-20 shown
8
Installation Guide for Dimming and Switching Panels
Side View:
Side View:
Surface Mount
Recess Mount
Air flow
No.
Max. Heat
Modules
BTUs (Kcal)/Hr.
1
90 (22.68)
2
170 (42.84)
3
250 (63.00)
4
330 (83.16)
5
410 (103.32)
6
490 (123.48)
7
570 (143.64)
8
650 (163.80)
9
730 (183.96)
C C a a u u t t i i o o n n ! ! This equipment is air-cooled. Vents
must not be blocked or you will void the
warranty.
C C a a u u t t i i o o n n ! ! 230 V
breakers are intended for industrial or
commercial use only.
Surface Mounting
• Lutron recommends using 1/4 in. (6 mm)
mounting bolts (maximum size accepted by
keyholes).
• Reinforce wall structure as required for weight and
local codes.
• Do not mount panel directly to wall board/drywall.
Recess Mounting
• Mount to wall stud by screwing through slots in
corners of panel.
• Mount panel between flush and 1/8 in. (3 mm)
below finished wall surface.
Recommended Mounting Heights*
(for LCP128 systems)
Mini
45 in. (1143 mm)
Standard
25 in. (635 mm)
* Measure from floor to bottom of panel;
optimal viewing height for controller.
Max. Weight w/o
Packaging
Pounds (kg)
24 (11)
35 (16)
37 (17)
68 (25)
71 (26)
74 (27)
77 (28)
80 (29)
83 (30)
panels with 13 A circuit