Lutron GRAFIK Eye GRX-CCO-8 Manual De Instrucciones página 4

Ocultar thumbs Ver también para GRAFIK Eye GRX-CCO-8:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 7
Set Number of MWT Channels (Zone Control Only)
If the Control Method is set to Scene Control, refer to Set Options – Scene Control.
The number of MWT channels may be set from 0 to 4. If the GRX-CCO-8 will not be controlling any
MWTs, set the number of channels to 0.
Set the number of channels using switches 1, 2, and 3 on the OPTIONS switch (see diagram
below).
ON
0 Channels
1
2
3
4
5
OPTIONS
ON
1 Channel
1
2
3
4
5
OPTIONS
ON
2 Channels
1
2
3
4
5
OPTIONS
Set Options – Zone Control
I
Set the OPTIONS switches to select the operating mode that is appropriate for your application.
I
The outputs may be set to either all momentary or all maintained.
I
The MWT channel(s) may be set to have Open and Close outputs, or Open, Stop and Close out-
puts. Refer to the manufacturer's MWT Controller Installation Guide to determine how many out-
puts per MWT channel are appropriate.
I
Set the appropriate Stop function. Refer to the manufacturer's MWT Controller Installation Guide.
I
Outputs not used as MWT channels may be controlled as individual outputs (e.g., if the GRX-
CCO-8 is set to have 2 channels of MWT controllers, and each channel has 2 outputs, then
there will be 4 outputs left over to act as individual outputs). The output will be closed when the
GRX Control Unit zone to which it is assigned has an intensity greater than zero.
ON
ON
1
2
3
4
5
OPTIONS
Output configura-
Open
Open
tion for MWTs
Close
Close
Maintained
Momentary
Output Type
Both outputs
Open and Close
Stop Function
opened
pulsed simultane-
ously*
* Please refer to Warning at the beginning of Set Options section.
GRX-CCO-8 Installation Instructions
ON
3 Channels
1
2
3
4
5
OPTIONS
ON
4 Channels
1
2
3
4
5
OPTIONS
ON
1
2
3
4
5
1
2
3
4
5
OPTIONS
OPTIONS
Open
Close
Momentary
Most recent out-
put pulsed
Note:
If channels are configured to have three outputs per MWT channel, then the maximum
number of MWT channels is two.
2 Outputs per Channel
1 2 3 4 5
1 2 3 4 5
COM +V MUX MUX
OPTIONS
ADDRESS
Set Options – Scene Control
Set the OPTIONS switches to select the GRX Control Unit scene range that is appropriate for
I
ON
your application. See the chart on the next page.
1
2
3
4
5
Set which scene applies which outputs. Only one output may be closed at any given time.
OPTIONS
I
Open
Stop
Close
Momentary
Dedicated Stop
output pulsed
4
3 Outputs per Channel
Close
Channel 4
Open
Close
Channel 3
Open
Close
Channel 2
Open
Close
Channel 1
Open
1 2 3 4 5
COM +V MUX MUX
OPTIONS
2 Individual Outputs
Close
Channel 2
Stop
Open
Close
Channel 1
Stop
Open
1 2 3 4 5
ADDRESS

Publicidad

Tabla de contenido
loading

Tabla de contenido