ABB ACS880-31 Serie Guía Rápida De Instalación página 144

Ocultar thumbs Ver también para ACS880-31 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 37
144
...G (R6)...
0.5 N·m (0.4 lbf·ft)
9
8
...G (R8)...
0.5 N·m (0.4 lbf·ft)
9
8
7
7
...G
XPOW External power input
Wire sizes:
1
+24VI
2
0.5 ... 2.5 mm
24 V DC, 2 A
2
GND
(24...14 AWG)
XAI
Reference voltage and analog inputs
Tightening
1
+VREF
10 V DC, R
2
-VREF
-10 V DC, R
torques: 0.5 N·m
3
AGND
Ground
(0.4 lbf·ft) for
4
AI1+
Speed reference 0(2)...10 V, R
both stranded
200 kohm
5
AI1-
and solid wiring.
6
AI2+
By default not in use. 0(4)...20 mA, R
7
AI2-
100 ohm
J1
J1
AI1 current/voltage selection jumper
J2
J2
AI2 current/voltage selection jumper
XAO
Analog outputs
1
AO1
Motor speed rpm 0...20 mA, R
500 ohm
2
AGND
3
AO2
Motor current 0...20 mA, R
4
AGND
XD2D
Drive-to-drive link
1
B
2
A
Drive-to-drive link
3
BGND
J3
J3
Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
11
NC
12
COM
13
NO
21
NC
22
COM
23
NO
Fault
31
NC
32
COM
33
NO
XD24
Digital interlock
1
DIIL
Run enable
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND Digital input/output ground
J6
Ground selection switch
XDIO
Digital input/outputs
1
DIO1
Output: Ready
2
DIO2
Output: Running
XDI
Digital inputs
1
DI1
Stop (0) / Start (1)
2
DI2
Forward (0) / Reverse (1)
3
DI3
Reset
4
DI4
Acceleration & deceleration select
5
DI5
Constant speed 1 (1 = On)
6
DI6
By default not in use.
XSTO
Safe torque off
1
OUT1
2
SGND
Safe torque off. Both circuits must be
3
IN1
closed for the drive to start.
4
IN2
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
1...10 kohm
L
1...10 kohm
L
>
in
=
in
<
L
< 500 ohm
L
Ready
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Faulted(-1)
250 V AC / 30 V DC
2 A

Publicidad

Tabla de contenido