Ul (Nec) Ratings; A - Install The Drive On The Wall - ABB ACS880-31 Serie Guía Rápida De Instalación

Ocultar thumbs Ver también para ACS880-31 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 37
12 EN – USA quick installation guide
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
abb.com/drives/documents.
Data

UL (NEC) ratings

ACS880-31
3-phase U
= 480 V (440, 460, 480 V)
N
07A6-5
EN
11A0-5
014A-5
USA
021A-5
027A-5
DE
034A-5
040A-5
ES
052A-5
065A-5
FI
077A-5
101A-5
FR
124A-5
156A-5
180A-5
FR
NL
Select the power cables
PL
See the
Data
PT
Ensure cooling
RU
See the
Data
operating temperature range of the drive without derating is -15 to +40 °C.
SV
Protect the drive and input power cable
TR
Check on the fuse time-current curve to ensure that the operating time of the fuse is
below0.1 seconds. Obey the local regulations.
ZH
A – Install the drive on the wall
See figure
A
on page 141.
Frames R6 and R8 of UL Type 12 (option +B056): Install an additional hood on top of
the drive before you tighten the upper fastening screws. Place the vertical edge of the
hood in between the wall and the drive back plate. Then tighten the screws to fasten
the hood and drive on its place. See figure
Cu cable
(AWG/kcmil)
14
14
10
10
8
8
6
4
2
2
1
2/0
3/0
250MCM
table on page 12.
table on page 12. No condensation or frost is allowed. The allowed
UL fuse
Losses (W)
JJS-15
JJS-20
JJS-25
JJS-35
JJS-40
JJS-50
JJS-60
JJS-80
JJS-90
JJS-110
JJS-150
JJS-200
JJS-225
JJS-300
3AXD00000588487
A (R6, R8)
on page 141.
219
278
321
473
625
711
807
960
1223
1560
1995
2800
3168
3872

Publicidad

Tabla de contenido
loading

Tabla de contenido