Lutron PowPak FCJS-010 Manual De Instalación
Ocultar thumbs Ver también para PowPak FCJS-010:

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

PowPak
Fixture Controls
®
Installation
Part of the Energi TriPak
Family
®
041507
Please read before installing.
Rev. A
09/2015
FCJS-010
120 – 277 V~ 50 / 60 Hz 1 A switching
0–10 V-
6 mA sink/source
FCJS-ECO
120 – 277 V~ 50 / 60 Hz 1A switching
Lutron
®
EcoSystem
14 V- 6 mA
®
PowPak
Wireless Fixture Control
®
UL 2043 Plenum Rated
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPakR fixture sensor
(FC-SENSOR or FC-VSENSOR).
*
For set-up, programming, and troubleshooting with a
Vive
system, please refer to the installation instructions
TM
included with the Vive
hub or at www.lutron.com
TM
Note for Replacement:
FCJS - the "S" model can replace the non-"S" model
Important Notes:
• For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
PowPak
®
Fixture Control
Install the fixture control directly to a fixture or
on a junction box nearest to the fixture. Install
the sensor on the ceiling near the fixture to
optimize coverage in the desired area.
Sensor
Fixture
30 ft (9 m)
Control
maximum
Pico
®
remote
control
Wireless sensors
and controls must
be located within
60 ft (18 m) line of sight,
or 30 ft (9 m), through walls, of
the associated control module.
Default Functionality
Wireless Controls: All lights
On: 100% ; Favorite: 50%; Off: 0%
Fixture Controls
Auto On level: FC-SENSOR only
(not applicable for FC-VSENSOR)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period: 15 minutes
For more information, see
www.lutron.com/TechnicalDocumentLibrary/369866.pdf
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each fixture, you will need:
At least one of these transmitters (22 total allowed)
One Fixture Control
PIR Lens
Raise
Load
Laser
Status
Detection
Daylight Lens
Toggle
LED
+
Lower
PowPakR Fixture Sensor
PowPakR Wireless Fixture Control
(FC-SENSOR or
(FCJS-010 or FCJS-ECO)
FC-VSENSOR)
(1 maximum)
Start Here
1
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the
conduit nut (provided) or with mounting screws (not provided). Please consult local and national
electric codes for proper installation.
A Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using the
adhesive strip (included). The two communication wires from the sensor attach to the fixture control
stab-in connectors. The wires are interchangeable to eliminate miswiring.
B Once installed, energize the control module. The fixture will turn on.
Line/Hot
(Black)
Green/Yellow
Neutral (White)
Neutral
Switched Line/Hot
(Red)
+
Violet (both FCJS-010 and FCJS-ECO)
Gray (FCJS-010) / Violet (FCJS-ECO)
Fixture/Troffer
or Junction
Box
1/2 in (21 mm) Knockout Opening
Conduit Nut
Important Note: To optimize RF performance of
the product:
– Keep the lamp wiring as short as possible to
reduce the radiation from the lamp wires.
– Keep the lamp wiring as far as possible from
the PowPakR Wireless Fixture Control mounting
location.
See the Troubleshooting section for more details.
Maximize Distance
From back
of sensor
Notes:
1. Control wires (Violet/Gray for FCJS-010 or Violet/Violet for FCJS-ECO) can be run
as either Class 1 or Class 2.
2. If hanging pendant fixtures the maximum wire length between fixture sensor and
fixture control is 12 ft (3.7 m). Sensor should be mounted no more than 2 ft (0.6 m)
from the fixture.
3. To install unit inside a junction box, please see Application Note 423 on
www.lutron.com
Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com
Notes:
1. Fixture control can be used
without a fixture sensor as long
as at least one Radio Powr
SavrT sensor or PicoR remote
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Radio Powr SavrT
Occupancy/Vacancy
Sensor
(10 maximum)
2
Associate Transmitters to Fixture Control
Before beginning this step, make sure that there are no other fixture controls being set up in the building which are currently in association
mode. It is possible that wireless transmitters from other systems can be incorrectly associated to this module.
A
Initiate association mode on the fixture control in one of two ways:
1 Press and hold the Toggle button " u " for 6 seconds on the fixture control until the load attached to the fixture control starts flashing
(every 2 seconds).
2 Alternatively, shine a green laser pointer (available at hardware or office supply stores) at the laser detection hole on the sensor until the load
attached to the fixture control starts flashing (every 2 seconds).
Note: Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next fixture control prior to
moving to Step 2B.
Fixture Earth
NEU
HOT
Ballast / Driver
+
!
WARNING
Eye injury and/or blindness hazard; avoid direct eye exposure to laser beam.
• Use of laser pointer is NOT recommended for use with Lutron
• DO NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or other shiny surfaces. DO NOT
view the laser beam through binoculars magnifying glass, or other optical devices.
• DO NOT allow children to use laser pointers.
• Read and follow the laser pointer manufacturer's instructions on safe use. In the event of injury, get medical attention immediately.
PowPakR Fixture Control Wiring
PowPakR Fixture Control Knockout
B Hold the indicated button on each transmitter for 6 seconds. The fixture
ce
will flash to show that wireless transmitters have been associated.
Alternatively, for Radio Powr SavrT occupancy/vacancy and daylight
Lamp Wiring
sensors, the green laser pointer can be used. See Application Note
#407 on www.lutron.com for more information. To associate another
transmitter, repeat steps 2A and 2B.
4. The fixture control needs to be accessible for some programming steps. Record
where it is mounted so that it can be easily located later.
5. When using a Radio Powr SavrT daylight sensor in conjunction with both a
PowPakR wireless fixture control and PowPakR fixture sensor, the Radio Powr
SavrT daylight sensor will provide the daylighting input to the control module, and
the PowPakR fixture sensor daylighting input will be ignored.
FCJS-010: At least one 0 – 10 V Fluorescent Ballast or LED Driver
FCJS-ECO: At least one Lutron
Consult the fixture installation guide for fixture wiring.
+
PicoR Remote
Radio Powr SavrT
6 mA maximum for the control lines. Switches up to 1 A total
Control
Daylight Sensor
(or maximum 3 ballasts or drivers). May be pre-installed in fixture.
(10 maximum)
(1 maximum)
*
OR
!
DANGER
products located near reflective surfaces.
®
Link
Test
6. When using a Radio Powr SavrT occupancy sensor in conjunction with both a
PowPakR wireless fixture control and PowPakR fixture sensor, occupancy data
from both sensors is used; either one detecting occupancy will turn the lights
on, and the lights turn off only when both sensors have gone vacant (no longer
detect occupancy).
7. For more information on the PowPakR fixture sensor, see: Document 369866 or
048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
EcoSystem
Ballast or LED Driver
®
®
Laser Detection
Green laser specifications:
• Wave output: constant
• Wavelength: 532 nm
• Output power:
5 mW maximum
Note: The fixture control
will automatically exit
association mode 10
minutes after the last
activity.

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Lutron PowPak FCJS-010

  • Página 1 Required Components PowPak Fixture Controls Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com ® For each fixture, you will need: Installation FCJS-010: At least one 0 – 10 V Fluorescent Ballast or LED Driver...
  • Página 2: Troubleshooting

    Lutron Electronics Co., Inc. Lutron, Pico, PowPak, EcoSystem, and Energi TriPak are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
  • Página 3 Composants requis Commandes de luminaires Assistance technique | 1.800.523.9466 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com Pour chaque luminaire, vous aurez besoin de : PowPak : Installation FCJS-010 : Au moins un ballast fluorescent ou un pilote de DEL de 0 – 10 V ®...
  • Página 4: Restaurer Les Réglages D'usine

    Lutron, Pico, PowPak, EcoSystem et Energi TriPak sont des marques déposées et Radio Powr Savr et Vive sont des marques de commerce de Lutron Electronics Co., Inc. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts.
  • Página 5: Módulo De Atenuación Powpak Instalación

    Componentes requeridos Módulo de Atenuación PowPak Asistencia técnica | 1.800.523.9466 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com ® Para cada artefacto, se necesitará: Instalación FCJS-010: Al menos un balasto fluorescente o controlador de LED de 0 – 10 V...
  • Página 6: Restablezca Los Valores Predeter- Minados De Fábrica

    Lutron Electronics Co., Inc. Lutron, Pico, PowPak, EcoSystem y Energi TriPak son marcas comerciales registradas y Radio Powr Savr y Vive son marcas comerciales de Lutron Electronics Co., Inc. NEC es una marca comercial registrada de la National Fire Protection Association, Quincy, Massachusetts.

Este manual también es adecuado para:

Powpak fcjs-eco

Tabla de contenido