Notices for installation
• E nsure the secure installation regardless of what type of wall on which it is installed, to prevent
potential dropping that could hurt people.

7.6 Electrical safety requirements

• B e sure to use the rated voltage and air conditioners dedicated circuit for the power supply, and the
power cord diameter must meet the national requirements.
• W hen the maximum current of air conditioner is ≥ 16A, it must use the air switch or leakage
protection switch equipped with protection devices.
• T he normal operating range is 90%-110% of the local rated voltage.
• T he minimum clearance between the air conditioner and the combustibles is 1.5 m.
• T he interconnection cord connect the indoor and outdoor units. You must first choose the right cable
size before preparing it for connection.
• C able types: Outdoor power cord: H07RN-F or H05RN-F; Power cable: H07RN-F or H05RN-F;
• M inimum cross-sectional area of power and power cables
North america
Appliance
amps(A)
10
13
18
25
30
40
• T he size of the interconnection cord, power cable, fuse, and switch needed is determined by the
maximum current of the unit. The maximum current is indicated on the nameplate located on the
side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.
C
Note: Core number of cable refer to the detailed wiring diagram adhered on the unit
which you purchased.
Split type wall mounted air-conditioner / Owner's Manual
AWG
18
16
14
12
10
8
Other regions
Rated current of
appliance (A)
> 3 and ≤ 6
> 6 and ≤ 10
> 10 and ≤ 16
> 16 and ≤ 25
> 25 and ≤ 32
> 32 and ≤ 40
Nominal cross-sectional
area (mm
)
2
0.75
1
1.5
2.5
4
6
31 / 220 EN