SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Generator Power Panel Receptacles

145 Model
185 Model
4.5 kVa/kW Peak
6 kVa/kW Peak
4 kVa/kW Continuous
5.5 kVa/kW Continuous
34/17 Amperes
40/23 Amperes
120/240 Volts AC
120/240 Volts AC
60 Hz
60 Hz
!
Use GFCI protection when operat-
ing auxiliary equipment. If unit does
not have GFCI receptacles, use
GFCI-protected extension cord.
!
Unplug power cord before attempt-
ing to service accessories or tools.
.
Generator power decreases as weld
current increases.
Set Weld Output control to maximum
for full generator power.
1
240 V 50 A AC Receptacle RC1
2
120 V 20 A AC Receptacles RC2
and RC3 (GFCI Receptacles Shown)
RC1 supplies 60 Hz single-phase power at
OM-248 551 Page 26
4
3
5
weld/power speed. See table for maximum
power output.
RC2 and RC3 supply 60 Hz single-phase
power at weld/power speed. See table for
maximum power output.
GFCI Receptacles
If a ground fault is detected, the GFCI Re-
set button pops out, red light turns on, and
the circuit opens to disconnect the faulty
equipment. Check for damaged tools,
cords, plugs, etc. connected to the recep-
tacle. Press button to reset receptacle and
resume operation.
.
At least once a month, run engine at
weld/power speed and press Test but-
ton to verify GFCI is working properly.
!
If GFCI red light blinks continu-
ously, replace receptacle.
.
Complete Parts List available at www.MillerWelds.com
1
3
Supplementary Protector CB1
CB1 protects receptacles RC1, RC2, and
RC3 from overload. If CB1 opens, the re-
ceptacles do not work. Place switch in On
position to reset.
4
Supplementary Protector CB2
5
Supplementary Protector CB3
CB2 protects RC2 and CB3 protects RC3
from overload. If a supplementary protector
opens, the receptacle does not work.
.
Press button to reset supplementary
protector. If supplementary protector
continues to open, contact Factory
Authorized Service Agent.
Combined output of all receptacles limited
to rating of the generator, see table above.
2
218 611−B