UNIT INSTALLATION
Minimum free clearance for maintenance access.
3 m
A
800 mm
MODEL
A
LOCATION
The unit must be installed on a firm level foundation,of adequate strength to support its full operating weight.
Vibration isolation such as rubber waffle pads should be installed between the unit and the supporting structure.
The unit must not be located where it will be subjected to heavy downpour of roof drainage and must be above
ground level in areas that are prone to stormwater flooding.
Minimum recommended height is :
250 mm above ground level.
When locating unit give consideration to, and locate unit as remote as possible from neighbour's sleeping areas
to minimise noise.
Service and air flow clearances must be allowed as indicated on the unit dimension sheet. It should be noted that
major service may require removal of the top panels. particular attention should be paid to avoiding obstructions
to the vertical condensor or air discharge which may result in recirculation of the outdoor air.
In addition to the service clearances noted on the dimension sheet it is essential that provision is made for adequate
and safe service access.
REFRIGERANT LINES
Refrigerant line installation, leak testing, evacuation and charging the system should be carried out by a qualified
refrigeration mechanic.
New, clean, moisture free refrigerant quality copper tube must be used.
Using specified diameter tubing, run liquid and gas lines from the outdoor unit to the indoor unit avoiding hot
surfaces such as hot water pipes, boilers, flues, etc...
The refrigerant piping should be run as short and straight as possible to obtain the most efficient performance.
A
A
A
Minimum free clearance (mm)
205
305 405M 405
500
9
3 m
A
505
605
755
905
800
A
A