Quick SBC NRG Serie Manual De Instalacion Y Uso página 14

Cargador de baterias sbc nrg
Ocultar thumbs Ver también para SBC NRG Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

NOTIFICATION SIGNS
GB
CONTROL PANEL
The control panel is made-up of three LEDS:
POWER LED, FLOAT LED and CHARGE LED
The information supplied by the LEDS are listed below:
IN THE ABSENCE OF PROBLEMS
LED STATE
IN THE PRESENCE OF PROBLEMS
LED STATE
14
DESCRIPTION
The battery charger is in the FLOAT phase.
The battery charger is in CHARGE status (BULK or ABSORPTION phase).
DESCRIPTION
Output short circuit or overload
Check the output wiring, the battery bank and the equipment connected to the battery
charger.
AC fail
The AC mains voltage is lower than 83 Vac.
The battery charger suspends the output power supply, which will start again once the
mains voltage will go back to a higher value than 83 Vac.
Overtemperature
The ambient temperature is higher than +70°C.
The battery charger suspends the output power supply, which will start again once the
ambient temperature is back to a lower value than +50°C.
Check the installation environment and its placement.
Output overvoltage
The battery charger, due to an internal malfunction, supplied for a very short time a
higher voltage than the rated value (the problem requires a check by a Quick customer
service).
CHARGE LED
FLOAT LED
POWER LED
SBC MINI LOW NRG - REV001B

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sbc 140 nrg frSbc 250 nrg frSbc 300 nrg frSbc 365 nrg fr

Tabla de contenido