Controller operation
System operation is set and monitored through the control settings.
The user interface allows navigating through the settings and modifying them.
Code
Level
Variable Name
Nr.
1
User
USER CONTROL
2
User
HOME ANTIFREEZE T° Home Antifreeze threshold T° value.
3
User
FREQ REDUCT
4
User
Room Hystersis
5
User
ADJUST T°ZONES
6
User
DAY PERIOD
TROOM SENSOR
7
User
ADJ ZONES
80AWX- 80AWH
16
DESCRIPTION
USER PARAMETERS
Use Days button for selection of below
0. Home Antifreeze option
0 : Disable
1 : Enable
1. Silent Mode
0: Not Active
1: Active
2. Power Off all the Electric Heater
0: Operating as normal
1: Electric heater disable
3. Specifies if domestic hot water is produced despite sensor
diagnostics or disinfection cycle failure
The code is self reset to 0 when the above problems are
solved
0: No
1: Yes
4. Specifies if the system is allowed to run only with backup
/ booster heaters when the Outdoor unit is in diagnostics
0. No
1. Yes
5. Domestic hot water BOOSTER: allows to heat up domestic
hot water electric heater regardless the heater schedule
The code is self reset to 0 once domestic hot water
setpoint is reached
0. Domestic hot water heater is turned on, if needed,
according to schedule
1. Domestic hot water heater is turned on, if needed,
regardless the schedule
6. Water Pump Management zone 1
0. Water pump of zone 1 does not stop when room 1
setpoint is reached
1. Water pump of zone 1 stops when room 1 setpoint is
reached
7. Water Pump Management zone 2
0. Water pump of zone 2 does not stop when room 2
setpoint is reached
1. Water pump of zone 2 stops when room 2 setpoint is
reached
Value of the Outdoor unit frequency reduction in %
Hysteresis on Room Temperature (see thermostat function)
Modifies maximum temperature of heating climatic curve
and minimum temperature of cooling climatic curve.
Use Days button for selection of below
0. Water set point adjustment in Heat mode for zone1
1. Water set point adjustment in Heat mode for Zone2
2. Water set point adjustment in Cool mode for zone1
3. Water set point adjustment in Cool mode for zone2
User can select how many period per day will be avaialble
for the scheduling.
Use days button for selecting the below.
Day 0 - Zone 1&2 Schedule
0. no schedule; no Schedule Icon will be displayed
1. 2 periods
2. 4 periods
3. 6 periods
Day 1 - Domestic hot water Schedule
1. 2 periods
2. 4 periods
Days button shall be used for the below selection
0. Room temperature sensor adjustment for zone1
1. Room temperature sensor adjustment for zone2
VALUE RANGE
DEFAULT
Min
Max
1
0
0
0
0
0
1
0
0
0
6°C
12°C
6°C
50%
100%
100%
0,1
2
0,5
-5°C
+5°C
0°C
3
1
3
2
-5°C
+5°C
0°C