12. Function
12.1 Approach the fitting.
• The water will flow.
12.2 Move away from the fitting.
• The water flow will stop automatically.
Temperature selection
13. Adjusting the range
The range can be adjusted using an ECC2 function controller via the web application.
14. Setting the hygiene flush
The hygiene flush can be adjusted with an ECC2 function controller via the web
application.
15. Thermal disinfection -manual-
This shower fitting offers thermal disinfection to reduce the risk of a legionella
infection.
The thermal disinfection process is triggered by overturning the thermostat.
Warning!
Personal protective measures (scald protection) must be implemented for the duration
of the thermal disinfection. This might include cordoning off the shower facilities.
Failure to observe this instruction can result in injuries due to scalding.
The operator is responsible for the execution, monitoring, and logging (room,
tapping point, date, time, temperature and duration).
The manufacturer does not accept any liability for claims by third parties relating to
the improper execution of thermal disinfection on the part of the operator.
The thermostat fitting has been prepared to carry out a thermal disinfection process
when the thermostat is overturned. The thermostat fitting can be manually thermally
disinfected (flushed with water at a temperature of 70°C) by unlocking the covered
stop on the temperature selector.