Motor With Brake; Auxiliary Relay Connection; Technical Data - Phoenix Contact ELR H5-ES-SC- 24DC/500AC-0,6 Manual Del Usuario

Controlador de arranque híbrido con función inversor
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 28

5.3. Motor with brake

If a motor with a brake (connection in the mechanical motor brake) is connected, the 400 V AC brake must
be connected to the 2/T1 and 6/T3 connections. A 230 V AC brake should be connected to the
4/T2 connection and the star point of the motor.
Please note: The motor current monitoring must be increased by the value of the brake
(nominal current brake).

5.4. Auxiliary relay connection

Auxiliary relay (e.g. PLC RSC 230UC/21, Order No.: 2966207) for activating the external brakes or
feedback to the PLC must be connected to the connections "4T2" and "N" of the system.

6. Technical data

Type
Input data
Rated control supply voltage U
Control supply voltage range
Control supply voltage
Rated control supply current as per IEC 60947-1
Control input L, R:
Output data
Block diagram
Rated operating voltage U
Operating voltage range
Load current at 20°C (see 8.2. Derating curve)
Load current at 20°C without safety function and
asymmetry recognition (see 8.2. Derating curve)
Rated operating current I
AC-51
AC-53a
Nominal switching performance
Leakage current (input, output)
Residual voltage at I
s
as per IEC 60947-1 / UL 508
Switching level "Safe off"
Switching level "Low" -3 ... 9.6 V DC
Switching level "Safe off" < 5 V DC
Switching level "High" 19.2 ... 30 V DC
Input current ≤ 5 mA
as per IEC 60947-1 500 V AC (50/60 Hz)
e
as per IEC 60947-1
as per UL 508
as per IEC 60947-1
e
as per IEC 60947-4-3
as per IEC 60947-4-2
as per UL 508
as per UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
e
Order No. ELR H5-ES-SC- 24DC/500AC-0,6
ELR H5-ES-SC- 24DC/500AC-2
ELR H5-ES-SC- 24DC/500AC-9
ELR H5-ES-SC-230AC/500AC-0,6
ELR H5-ES-SC-230AC/500AC-2
ELR H5-ES-SC-230AC/500AC-9
ELR...-24DC/...
24 V DC
19.2 ... 30 V DC
(32 V DC, max. 1 min.)
< 5 V DC
≤ 40 mA
load side ELR...-0.6
Safety end level with bypass, three-phase
electrically isolated switch-off
42...550 V AC
42...500 V AC
0.075...0.6 A
0... 0.6 A
0.6 A
0.6 A
0.6 A
0.3 kW (0.4 HP)
0.5 kW (0.6 HP)
0 mA
< 200 mV
ELR...-230AC/...
230 V AC (50/60 Hz)
85 ... 253 V AC
< 5 V AC
≤ 4 mA
< 44 V AC
< 5 V AC
85 ... 253 V AC
≤ 7 mA
ELR...-2
ELR...-9
0.18...2.4 A
1,2... 9.0 A
0...2.4 A
0...9.0 A
2.4 A
9 A
2.4 A
6.5 A
2.4 A
6.5 A
0.9 kW (1.2 HP)
2.3 kW (3.0 HP)
1.7 kW (2.2 HP)
4.6 kW (6.1 HP)
0 mA
0 mA
< 300 mV
< 500 mV
2900558
2900559
2900561
2900688
2900560
2900562
17

Publicidad

Tabla de contenido
loading

Tabla de contenido