4 • OPERATION AND PROGRAMMING
2.2. Testing and disabling wired alarm groups:
Select the appropriate alarm group with [ ] or [ ]
- [Test] allows you to test the selected alarm group or all alarm groups
- [Inaktiv] (inactive) switches off the selected alarm group
Programming:
Select the appropriate alarm group with [ ] or [ ] and confirm with [OK]
- [Name] allows you to enter a customer-specific alarm group name
- Each time you press the [Vorlagen] (templates) button, it calls up 10 different saved texts, which can be changed with [ ],
[ ], [ ], [ ] or accepted with [OK]
- [Status] changes the type of alarm group monitoring. The active status is shown on the display:
NO = the alarm group is open in idle mode and closed in alarm status
NC = the alarm group is closed in idle mode and open in alarm status
EOL NO = conventional technology with end of line termination. The alarm group is terminated with a terminal resistor in the last
detector. Make sure to check the polarity (red = + black = -). Connected
detectors must charge each alarm group with 1.2 kOhm in alarm status.
Advantage of conventional technology with end of line termination: the alarm group is also monitored for wire breaks and short
circuits.
NB: alarm group 11 can only be operated as an NO alarm group.
- [Typ] (type) defines the alarm group as shown when triggered. There is a choice between fire, house alarm, gas alarm, technical
alarm and evacuation alarm.
NB: alarm group 11 can only be operated as a house alarm group. The LED display of the call point is not controlled.
If the LED display of the call point is indispensable, please use one of alarm groups 7 – 10.
- [Delay] and [ ], [ ] sets the verification time in seconds. When activated, the verification time starts immediately and the control
centre switches to prealarm state for the duration of the verification time. Once the verification time has elapsed, the main alarm
is triggered and the sounder activated. In addition, [Delay] must be activated for the sounders in menu 3. Outputs. This gives the
site operator the opportunity to check the alarm on-site and switch if off, where necessary, using [Akustik AUS] (acoustic OFF)
before the main alarm is triggered. If the verification time is 0s, the main alarm is triggered immediately.