• Pre-flashing time:
A manoeuvre warning sign can be activated on the flashing light
before each manoeuvre begins, and the time programmed to 1, 2,
4, 6, 8 and 10 seconds.
• Current sensitivity:
The control unit is equipped with a system which measures the
current absorbed by the two motors used to detect the mechani-
cal stops and any obstacles when the gate is moving. Since the
current absorbed depends on a number of conditions, including
the weight of the gate, friction, wind and variations in voltage, the
cut-in threshold can be changed.
There are 6 levels: 1 is the most sensitive (minimum force), 6 is the
least sensitive (maximum force).

7) Programming

All the functions described in the "Programmable functions" chapter
can be selected by means of a programming phase which terminates
by memorising the choices made.

7.1) Programming methods

The P1, P2 and P3 buttons are used for all the programming phases, while the 5 Leds (L1, L2...L5) indicate the selected "parameter".
There are two different programming levels:
• At level 1, the functions can be activated or deactivated. Each Led (L1, L2...L5) corresponds to a function: if the Led is on, the function is
active; if it is off, it is deactivated.
Level one consists in 2 parts which can be selected using the P3 button. The corresponding LED P3 indicates which of the 2 parts has been
selected.
Level one (fixed LED P1): part one - (LED P3 off)
Led L1
Led L2
Automatic
"Condominium" Pre-flashing
closing
function
• It is possible to pass to the second level from level one of part one. At this second level the user can choose the parameter relating to the
function. A different value corresponds to each LED which must be associated to the parameter.
Level one (fixed LED P1): part one - (LED P3 off)
Led L1
Led L2
Automatic
"Condominium" Pre-flashing
closing
function
Second level:
Parameter:
Parameter:
Pause Time
AUX Input
L1: 5s
L1: Open
partially type 1
L2: 10s
L2: Open
partially type 2
L3: 20s
L3: Open only
L4: 40s
L4: Close only
L5: 80s
L5: Photo 2
All LEDs off:
input not used
Led L3
Led L4
Led L5
Close
Opening delay
after photo
Led L3
Led L4
Led L5
Close
Opening delay
after photo
Parameter:
Parameter:
Parameter:
Pre-flashing
Current
Leaf Delay
Time
sensitivity
L1: 2s
L1: Level 1
L1: 5%
(most sensitive)
L2: 4s
L2: Level 2
L2: 10%
L3: 6s
L3: Level 3
L3: 20%
L4: 8s
L4: Level 4
L4: 30%
L5: 10s
L5: Level 5
L5: 40%
(least sensitive)
All LEDs off:
level 6
(max. current
sensitivity)
!
If the "current sensitivity" function (together with oth-
er vital features) is adjusted correctly, the system will
comply with European standards, EN 12453 and EN
12445, which require techniques or devices to be used to
limit force and danger during the functioning of automat-
ic gates and doors are moved.
• Leaf delay:
The delay in starting up the motor of the lower leaf can be pro-
grammed to 5, 10, 20, 30 or 40% of the working time.
The control unit therefore has a memory which stores the functions
and parameters relative to the automation process.
Level one (fixed LED P1): part two - (LED P3 on)
Led L1
Led L2
Led L3
Phototest
Electric Lock
Resistive STOP Heavy gates
Level one (fixed LED P1): part two - (LED P3 on)
Led L1
Led L2
Led L3
Phototest
Electric Lock
Resistive STOP Heavy gates
Led L4
Led L5
Proportional
Open Gate
Led L4
Led L5
Proportional
Open Gate