Dell PowerVault 51F Guia De Instalacion página 23

Interruptor de canal de fibra de 8 puertos
Ocultar thumbs Ver también para PowerVault 51F:

Publicidad

Idiomas disponibles

Idiomas disponibles

+   #    
To install the switch in the rack, perform the following steps:
1.
Extend both intermediate slides forward until they lock in the extended position.
2.
At the front of the rack, carefully align the switch's inner-slide rails with the inter-
mediate slides.
Slide the inner-slide rails into the intermediate slides, as shown in Figure 1-6.
Press the green button on the outside of each intermediate slide so that the
switch slides to the middle position. Press the green button again so that the
switch slides to its final position and locks in place.
intermediate slide
switch
manifold
bezel
thumbscrews (2)
 + ' $$(,  
3.
Make sure that there is no gap between the manifold and switch.
4.
Tighten the eight 10-32 x 1/2-inch screws that attach the outer slides to the rack.
5.
Tighten the two thumbscrews on the bezel to keep the switch and slide assem-
bly from sliding out of the rack.
The thumbscrews pass through the holes in the rack and into the middle holes of
the stationary brackets.
inner-slide rail
outer slide
green button
Rack Installation Guide
1-7