11
Derivative Time
Normally ¼ of integral time.
0.0...999.9 seconds. Derivative 0 disabled. > Default: 0.0.
12
Cycle Time
Cycle time (for P.I.D. on contactor 10"/15", for P.I.D. on SSR 1")
1...300 seconds. > Default: 10.
13
Command State Error
SContact status for command output in case of error.
Open Contact > Default
Closed Contact
14
Visualization Display 2
Set visualization on display 2 during a cycle
(End Step Setpoint) End temperature of operating step
(Real Setpoint) Updated according to the selected gradient
(Cycle Number) Number of operating cycle. > Default
(Step Number) Number of operating step
Time elaplsed from cycle start
15
Delayed Start
Enables initial waiting for delayed start of cycle
(Disabled) Initial waiting disabled. > Default
(Enabled) Initial waiting selectable by the user.
16
Special Functions
Enables "simple controller" function.
(Disabled) No function available. > Default.
(Thermoregulator) Enables thermoregulator function.
17
Hold Function
Enables "Hold" function; allows to hold the cycle and modify setpoint by
keyboard.
(Disabled) "Hold" function disabled. > Default.
(Enabled) "Hold" function enabled.
26
ATR902 - User manual