Pixsys ATR 902 Manual Instalador página 26

Ocultar thumbs Ver también para ATR 902:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles


11
Derivative Time
Normally ¼ of integral time.
0.0...999.9 seconds. Derivative 0 disabled. > Default: 0.0.

12
Cycle Time
Cycle time (for P.I.D. on contactor 10"/15", for P.I.D. on SSR 1")
1...300 seconds. > Default: 10.

13
Command State Error
SContact status for command output in case of error.

Open Contact > Default

Closed Contact

14
Visualization Display 2
Set visualization on display 2 during a cycle

(End Step Setpoint) End temperature of operating step

(Real Setpoint) Updated according to the selected gradient

(Cycle Number) Number of operating cycle. > Default

(Step Number) Number of operating step

Time elaplsed from cycle start

15
Delayed Start
Enables initial waiting for delayed start of cycle

(Disabled) Initial waiting disabled. > Default

(Enabled) Initial waiting selectable by the user.

16
Special Functions
Enables "simple controller" function.

(Disabled) No function available. > Default.

(Thermoregulator) Enables thermoregulator function.

17
Hold Function
Enables "Hold" function; allows to hold the cycle and modify setpoint by
keyboard.

(Disabled) "Hold" function disabled. > Default.

(Enabled) "Hold" function enabled.
26
ATR902 - User manual