3. Open the differential pressure valve (
4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve
6. Open the other differential pressure valve (

Commissioning for liquids

Usual arrangement
Pressure transmitter
Stabilizing valve
Differential pressure valves
,
Differential pressure lines
Shut-off valves
Transmitter below the differential pressure
transducer
Condition
All valves are closed.
Procedure
WARNING
The transmitter should not be depressurized if toxic substances are being used.
To commission the transmitter with liquids, proceed as follows:
1. Open both the shut-off valves
2. Open the stabilizing valve
14
or
).
.
or
at the pressure tapping point.
.
).
Special arrangement
Drain valves
Gas collector vessels (optional)
Differential pressure transducer
Vent valves
Transmitter above the
differential pressure transducer