Transmitter above the differential pressure
transducer
Condition
All shut-off valves are closed.
Procedure
To commission the transmitter for gases, proceed as follows:
1. Open both the shut-off valves
2. Open the stabilizing valve
3. Open the differential pressure valve (
4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve
6. Open the other differential pressure valve (
5.4.3
Commissioning for liquids
Usual arrangement
①
Pressure transmitter
②
Equalizer valve
③
④
Differential pressure valves
,
⑤
Differential pressure lines
⑥
Shut-off valves
Transmitter below the differential pressure
transducer
28