Testing The Connection - Zodiac Pool Systems Jandy AquaPure Serie Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Page 16
7. The Jandy
AquaLink
®
wired up to 152.4 m (500 ft) apart. Any outdoor rated four conductor cable, minimum 0.33 mm
be used. Locate the appropriate screw terminals on the circuit board and wire the power pack to the AquaLink RS
or PDA red 4-pin terminal bar (see Figure 21).
NOTE The screw terminals on the AquaLink RS or PDA are removable to aid in installation.
Terminal Bar
Figure 21.
Communication Wiring between Power Pack and AquaLink RS Control System or PDA Network

3.6.3 Testing the Connection

Once the power pack has been wired to the AquaLink RS Control System or PDA, follow these steps to test the
connection:
1. Apply power to the power pack and the AquaLink RS Control System or PDA.
2. Wait about 20 seconds. If the connection was successful, a Ŧ symbol will appear in the top right corner of the
power pack display.
NOTE If the power pack does not connect to the controller, turn the power off to both devices and repeat steps 1
and 2. If the power pack still does not connect to the controller, re-check the wiring connections (see Section
3.6.2) and the controller setting on the power pack (see Section 3.6.1).
RS or PDA and power pack use a four (4) wire connection to communicate and can be
®
Red, 4-Pin
4 3 2 1
OPTIONAL
Jandy
Power Center
Power Pack
GRN
YEL
BLK
RED
(22 AWG), can
2

Publicidad

Tabla de contenido
loading

Productos relacionados para Zodiac Pool Systems Jandy AquaPure Serie

Este manual también es adecuado para:

Apure35Apure35c

Tabla de contenido