Product Description; Product Overview; Product Name; Technical Data - Lowara Q-Smart Manual De Instalación, Funcionamiento Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 118
en - Original instructions
3

Product Description

3.1

Product overview

The Q-SMART control panel is a single-phase elec-
tronic control panel intended to be used with 1 or 2
single-phase electric pumps for different fixed speed
applications.
It is suitable for pressurisation, emptying or sewage
systems. Check your type of installation and change
the parameters (see sections 5.4.3,
accordingly.

3.2 Product name

Example: Q-SMART 10/15/D 12A
Q-
Trade name of control panel.
SMART
Mains power supply, single-phase
1x230Vac 50/60Hz
10
Number of pumps that can be con-
nected
10: One
20: Two
15
Nominal motor power kW x 10
15=1.5kW x 10
D
Default software application
D: sewage/lifting
B: booster/pressurisation
12A
Maximum current absorbed by one
electric pump

3.3 Technical data

Tab 1
Standard version
Control
panel
Q-SMART 10
model
Rated
voltage
1x230VAC (-15% to +10%)
input (Uin)
Rated input fre-
quency
Rated input cur-
1
rent
12A
(Uin=230V)
Recommended
20A
2
line protection
Rated
output
current
12 A
(Uin=230V)
Consumption in
(standby power may vary ac-
standby
cording to the type of sensor
Type of load
Nominal Cosø
Box
Self-extinguishing - grey
Frontal IP Pro-
tection
Connections
(use
copper
(power supply, input and output)
conductor only)
Maximum input
power
cable
section
34
5.4.4
and 10.1)
Q-SMART 20
50/60 Hz
24A
40A
2 x 12 A
1.8W
connected)
Electric motor
≥ 0.6
55
Screw terminal blocks
2
4 mm
Maximum motor
power
cable
section
Pressure: 0 to 60 bar (0 to 6
3
Set point
Level: 0 to 50 m (0 to 164 feet)
Temperature: -20 to 100°C (32
Ambient
tem-
0 to 40°C (32 to 122°F)
perature
Ambient Humidi-
10 to 90% non-condensing
ty
4
Altitude
Alarm buzzer
Motor protection
fuse F1, F2
Auxiliary protec-
1A Time-Lag 5 x20 mm
tion fuse F3
(T1L 250V IEC60127-2/3)
5 multifunctional inputs for
Digital inputs
NO/NC contact (voltage-free,
4 level electrode sensors,
Electric
Probe
Sensitivity: 5 to 100kOhm,
inputs
Line capacity: 10nF max,
Electrode voltage: 6.5V - 20Hz
Transducer 0-20/4-20mA
(Sensor active value input)
Analogue input
Current input 0-22 mA, accuracy
Sensor power supply +12 Vdc
1 Load relay
Digital outputs
Maximum current allowed for
the electric motor is 12A
Port for communication with the
supervision system via TTL with
TTL Serial port
ModBus communication proto-
Signals: +5V, RX, TX, RTS, 0V
Port RJ45 for communication
with the card with voltage-free
RJ45 connector
Signals: +12V - 120mA , 0V,
6 open collector outputs
Dimensions and
Weight
1.
The current supplied by the control panel shall
not be lower than the current absorbed by the
electric pumps, and depends also on the volt-
age drop due to the length of the cable.
2.
Choose the current of the line protection device
in relation to the maximum current absorbed by
the motors.
3.
Only if the electronic sensor is used.
4.
For higher altitudes or other environmental con-
ditions not covered in this manual, please con-
tact your local After Sales / Service representa-
tive.
2
4 mm
MegaPa)
to 122°F)
≤2000m asl
3.6kHz, Piezo
12 A (gG)
12V, 4mA )
1 reference electrode
0.3%,
2 Load relays
30(15)A @ 250VAC
col
relays
See Figure
3

Publicidad

Tabla de contenido
loading

Tabla de contenido