en - Original instructions
tomatic
mode.
c16
Insert the
1= Pump 1
duty pump
2= Pump 2
that you
want to
start first
after power-
ing up of
the set or
after reset.
Parameter
c15 is ena-
bled.
If Jockey
pump is
installed
(c02=1) the
first pump is
default P1.
c17
If automatic
0=
pump rota-
bled
tion does
1
not take
hours
place (the
system has
never been
able to
stop), after
the set time
a "forced"
rotation of
the duty
pumps is
performed.
c18
Settable
0=
only for
bled
system with
1= Enabled
sensor.
Halves the
timing (t10,
t11, t12,
t13) in the
case of
excessive
variation of
the feed-
back (pres-
sure, levels,
tempera-
ture).
REAL TIME CLOCK
h19
Setting the
Y
date
h20
Setting the
M= 1 to 12 -
month
h21
Setting the
d= 1 to 31
day
h22
Setting the
h= 0 to 23
hour
h23
Setting the
m= 00 to
minute
59
50
-
1
Disa-
Hours 0
to
12
Disa-
-
0
-
-
-
-
AUTO-TEST RUN
With this function, the pumps are started once per
week and at a set time and day. For a description
see section 8.1.
c24
Enabling
0= Disa-
periodic
bled
Auto-test
1= Weekly
t25
Setting the
1 to 30
inactivity
days
period of
pump 2
(c24=2)
h26
Setting the
1= Monday
day of
2= Tuesday
weekly au-
3=
to-test
Wednesday
(c24=1)
4= Thurs-
day
5= Friday
6= Satur-
day
7= Sunday
h27
Setting the
0 to 23
hour of
weekly au-
to-test
(c24=1)
h28
Setting the
0 to 59
minutes of
weekly au-
to-test
(c24=1)
h29
Setting the
0 to 300
operating
time of the
pump dur-
ing the
weekly au-
to-test
(c24=1)
CHANGING THE SET POINT (only for system
with analogue sensor)
c30
Setting the
0= Disa-
mode to
bled
change the
1= Internal
set point
clock
2= With
program-
mable digi-
tal input D
IN_PROG
r30
Setting the
0 to full
value for
scale
changing
the set
point. The
-
0
days
1
-
1
hour
10
min
00
sec
60
-
0
vari-
0.5
ous