Description
A55
Max threshold alarm
Troubleshooting:
The pressure of the system exceeds the set value of
the Maximum threshold parameter (r55).
After the delay time par t55 all the pumps are
stopped.
The alarm is excluded in manual mode.
Causes/solutions
The pressure has exceeded the max pressure:
check the set value (r55).
Wrong pump selection: replace the pump.
Description
A56
The same alarm is detected
5 times in the last 30 minutes
Troubleshooting:
The system is blocked because the same alarm is
detected 5 times in the last 30 minutes. Use parame-
ter c57 to reset and restart the system.
Causes/solutions
Identify the type of alarm and resolve it
10 SYSTEM SETUP AND
OPERATION
10.1 Parameters to check upon startup
Check the following programming parameters upon
startup.
1.
Define the installation and proper control devic-
es (sensor, digital inputs):
o
1 booster pump, refer to figures
o
2 booster pumps, refer to figures
o
1 sewage or filling pump, refer to figures
43
to 52.
o
2 booster pumps, refer to figures
2.
Connect the sensor and digital input to the
proper terminals. Refer to figures 7,
o
1 booster pump, refer to figures
o
2 booster pumps, refer to figures
o
1 sewage or filling pump, refer to figures
43
to 52.
o
2 booster pumps, refer to figures
3.
Select the software during power-up, section
5.4.3.
o
sewage or filling pump = sE software.
o
booster pump = bS software.
4.
Set the parameters in the parameter menu ac-
cording to the type of application and pump:
o
sewage or filling pump (sE software), see
Tab
2.
o
booster pump (bS software), see
Reset
11 MAINTENANCE
Auto
Precaution

11.1 General maintenance

Reset
Manual
11
to 26.
27
to 42.
53
to 62.
8
and 9.
11
to 26.
27
to 42.
53
to 62.
Tab
3.
WARNING:
Observe the accident prevention
regulations in force.
Use suitable equipment and pro-
tective devices.
Always refer to the local regula-
tions, legislation and codes in force
regarding the selection of the in-
stallation site, plumbing and power
connection.
Electrical hazard
Before any servicing or maintenance,
disconnect the system from the power
supply and wait at least 2 minutes be-
fore starting work on or in the unit.
Turn off and unplug the system before
installing the unit or carrying out
maintenance.
The Q-SMART control panel does not require
any routine maintenance when used within the
limits that are indicated in the
It is advisable to periodically check correct trig-
gering of the high sensitivity differential switch
(30 mA) [RCD, residual current device] suited to
the ground fault current.