5.3 Start-up and programming

NOTICE:
The control panel is delivered already pro-
grammed with the default values.
SOFTWARE DEFAULT IS SEWAGE (SE),
see section 5.4.3.
Edit the values according to the type of
electric pump and system, see section
5.4.4
and refer to figures
If the control panel is already fitted with an
electric pump, it has been programmed in
relation to the characteristics of the electric
pump. Edit the function values of the sys-
tem.
Incorrect configuration can damage the
electric pump and/or the system.
Refer to figures
1
and
2
1.
Check that all the mechanical, electrical and
hydraulic connections have been made. See
Mechanical installation
installation
section 4.3.
2.
Turn on the power at the main switch (1) figure
7 and the control panel starts up.
3.
The control panel performs an internal hardware
Auto-test and the LED (9) turns on. It is possible
to enter the CONFIGURATION MENU to set the
proper application (refer to figures
NOTICE:
The Q-SMART control panel is set in MAN-
UAL mode upon initial start-up. The mode
when the control panel is powered up is the
last selected before power-off, and can be
AUTOMATIC or MANUAL.
In automatic mode, the electric pump runs if
the pressure, level or temperature of the
system is below the value selected. If nec-
essary, press (4) to set MANUAL mode and
the electric pump turns off if running.
The parameters in the PARAMETER menu can be
edited ONLY in STANDBY (StY) mode. Press (4)
to switch between AUTOMATIC or MANUAL and
STANDBY (StY) mode; the LEDs (5) and (2) are off.
See section
5.4.4
for the proper procedure.
5.4 Programming
The control panel has three menus that can be ac-
cessed with a combination of keys:
ALARMS LOG (see section 5.4.2).
CONFIGURATION (see section 5.4.3).
PARAMETERS (see section 5.4.4).
5.4.1
Texts shown on the display
Sim
Description
Operation Manual mode: pump is
MAn
stopped
Aut
Operation Automatic mode.
40
11
to 62.
for the user interface.
section 4.2,
Electrical
11
to 62).
Standby mode: Programming is ena-
StY
bled
cnf
Software selection (sE or bS)
Q-SMART control panel is set in Sew-
sE
age mode.
Q-SMART control panel is set in Pres-
bS
surisation/booster mode
c
Configuration parameter
t
Timing parameter
r
Adjustment parameter menu
h
Hour and Data value
Shown on display when the analogue
---
sensor is not used. The digital sensor is
used.
When the analogue sensor is not used
run
(no feedback), the pump is running
A

Alarm log

tSt
Auto-test running
Q-SMART control panel is disabled by
the external command switch connect-
OFF
ed to the D IN PROGR (figure 9)
The status of the alarm in the alarm log.
On
The status of the alarm in the alarm log.
P1
Pump 1 runs
P2
Pump 2 runs
5.4.2
Alarm log
It is possible to view information concerning any
alarms in either MANUAL or AUTOMATIC mode.
The menu is read-only and displays the last 20
alarms that have occurred.
Refer to figures
2
and 9.
- Press and hold (4) for a few seconds to access the
menu. The LED (4) switches off.
- Press (1) or (2) to select the alarm, and press (5)
to confirm.
- Press (5) several times and the following data are
displayed in sequence: alarm code, status (OFF,
ON), and day, month, year, hour, minute, to indi-
cate the time of occurrence.
- Press (4) to exit or (1) or (2) to select another
alarm in the list.
Example in figure 63.
Alarm number 20, type A53,
- deactivated (OFF) 12/11/2015 at 21h:36m
- activated (ON) 12/11/2015 at 20h:58m
5.4.3

Configuration menu

This is used to select the software application (refer
to figures
11
to 62).
SELECTION MUST BE DONE ONLY DURING
POWER-UP.
1.
Refer to figure 6: Turn on the main switch (2).
2.
Refer to figures
1
and 2: Press buttons (1) and
(2) at the same time during power-up; LED (9) is
illuminated and "cnf" appears on the display.
3.
Press (5), and the actual configuration is shown.
4.
Press (1) or (2) to edit the software.