Figure B
Please ensure that the following steps are taken:
Unit installation should be tilted at least 10mm as recommended in Figure B.
The drain pipe slope shall be kept at least 1:100.
Provide clearance for easy servicing and optimal air flow as shown in Figure C.
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Figure C
Nut
Washer
Washer
Nut
400mm or more
Floor Standing Type
Hanger Bracket
Indoor Unit
250mm or less
300mm
(Min.)
1-4
Ceiling
Drainage Pipe
Utensils, furnitures or built-in
architectural features must not
protrude more than 250mm
Floor
1m or more