Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

(A)
(B)
GAS BURNERS AND RELEVANT GAS TRAINS APPROVED ACCORDING TO EN 676
Gas train L
Ø
C.T.
Code
1"
-
3970145
1/2
1"
-
3970180
1/2
2"
-
3970146
2"
3970160
2"
-
3970181
2"
3970182
DN 65
-
3970147
DN 65
3970161
DN 80
3970148
DN 80
3970162
(C)
GAS TRAIN COMPONENTS
Code
Filter
5
3970145
GF 515/1
3970180
3970146
GF 520/1
3970160
3970181
3970182
3970147
GF 40065/3
3970161
3970148
GF 40080/3
3970162
Burner
RS 70
RS 100
RS 130
-
-
-
-
Components
Pressure governor
6
FRS 515
Multiblock MB DLE 415
FRS 520
Multiblock MB DLE 420
FRS 5065
FRS 5080
D722
D953
13
14
Code
Code
3010123
3000843
3010123
3000843
3010123
-
-
-
3010123
-
-
-
3010123
3000825
-
3000825
3010123
3000826
-
3000826
Solenoids
8 - 9
DMV-DLE 512/11
DMV-DLE 520/11
DMV-DLE 5065/11
DMV-DLE 5080/11
8

GAS LINE

• The gas train must be connected to the gas
attachment 1)(A), using flange 2), gasket 3)
and screws 4) supplied with the burner.
• The gas train can enter the burner from the
right or left side, depending on which is the
most convenient, see fig.(A).
• Gas solenoids 8)-9)(B) must be as close as
possible to the burner to ensure gas reaches
the combustion head within the safety time
range of 3 s.
• Make sure that the pressure governor calibra-
tion range (colour of the spring) comprises the
pressure required by the burner.
GAS TRAIN (B)
It is type-approved according to EN 676 Stand-
ards and is supplied separately from the burner
with the code indicated in Table (C).
KEY (B)
1 - Gas input pipe
2 - Manual valve
3 - Vibration damping joint
4 - Pressure gauge with pushbutton cock
5 - Filter
6 - Pressure governor
7 - Minimum gas pressure switch
8 - Safety solenoid
9 - Adjustment solenoid
Two adjustments:
• ignition delivery
• maximum delivery
10 - Standard issue burner gasket with flange
11 - Gas adjustment butterfly valve
12 - Burner
13 - Gas valve 8)-9) leak detection control
device.
In accordance with EN 676 Standards, gas
valve leak detection control devices are
compulsory for burners with maximum out-
puts of more than 1200 kW; therefore only
for model RS 130.
14 - Gas train/burner adaptor.
P1 - Pressure at combustion head
P2 - Pressure down-line from the pressure gov-
ernor
P3 - Pressure up-line from the filter
L - Gas train supplied separately with the code
indicated in Table (C)
L1 - The responsibility of the installer
KEY TO TABLE (C)
C.T.=Gas valves 8) - 9) leak detection control
devices:
- = Gas train without gas valve leak detec-
tion control device; device that can be
ordered separately and assembled sub-
sequently (see Column 13).
= Gas train with assembled VPS valve
leak detection control device.
13 = VPS valve leak detection control device.
Supplied separately from gas train on
request.
14 = Gas train/burner adaptor.
Supplied separately from gas train on
request.
Note
See the accompanying instructions for the
adjustment of the gas train.
(vertical)
VS
(vertical)
VR
(vertical)
(rapid opening)
(slow opening)

Publicidad

Tabla de contenido
loading

Tabla de contenido