Assembly And Preparation; Selecting An Installation Location; Installation Space - NEW ENERGY KACO blueplanet 87.0 TL3 Instrucciones De Operación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 81
Output levels (AC)
Voltage range: continu-
EN
ous operation
Max. voltage range (up to
100 s)
Nominal current
5

Assembly and preparation

5.1

Selecting an installation location

Risk of fatal injury due to fire or explosions
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
Property damage due to gases that have an abrasive effect on surfaces when they come into contact
with ambient humidity caused by weather conditions!
The housing of the device may be seriously damaged by gases (ammonia, sulfur, etc.) if it comes into con-
tact with ambient humidity caused by weather conditions.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavorable structural or mounting conditions shall be billed to the cus-
tomer.

Installation space

ž As dry as possible, climate-controlled, the waste heat must be dissipated away from the device.
ž Unobstructed air circulation.
ž Close to the ground, accessible from the front and sides without requiring additional resources.
ž Protected on all sides against moisture and dust penetration and direct sunlight (thermal heating) in outdoor areas.
Implementation where necessary via constructional measures, e.g. wind breaks.
Installation surface
ž Must have adequate load-bearing capacity
ž Must be accessible for installation and maintenance
ž Flame-retardant
ž Minimum clearances to be observed during installation: [See figure 10] [} Page 14]
Page 12
300 V - 580 V
300 V - 580 V
625 V
625 V
3 x 132.3 A
3 x 132.3 A
DANGER
Do not mount the device in an area at risk of explosion or in the vicinity of highly flammable materials.
CAUTION
ü If the device is exposed to gases, it must be installed in a location that is visible.
Perform regular visual inspections.
Immediately remove any moisture from the housing.
Ensure that there is sufficient ventilation at the installation location.
Immediately remove dirt, especially on vents.
Failure to observe these instructions may result in damage to the device which is not covered by the
warranty.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
300 V - 580 V
480 V - 760 V
625 V
825 V
3 x 132.3 A
3 x 120.3 A
KACO blueplanet 137 TL3 KACO blueplanaet 150 TL3
480 V - 760 V
480 V - 760 V
825 V
825 V
3 x 132.3 A
3 x 131.2 A

Publicidad