6.7

Establishing additional equipotential bonding

EN
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
↻ The device has been installed on the mount.
1 Remove the insulation from the equipotential bonding line.
2 Furnish the stripped cable with an M8 ring cable lug.
3 Place the earth cable at the earthing point and secure it with an additional M8
nut and lock washer [W_17 /
» The housing is included in the equipotential bonding.
6.8

Sealing the connection area

↻ The grid connection has been prepared.
1 Lift the housing cover onto the housing and loosely tighten the fastening screws.
2 Secure the housing cover by tightening all 6 screws in a diagonally opposite se-
quence [ T_25/
» The device has been mounted and installed.
» Put the device into operation.
Page 22
10 Nm].
4.8 Nm].
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Fig. 18: Additional earthing point
1 Earthing bolt
2
Fig. 19: Closing the housing cover
1
Housing cover
3
Screws
KACO blueplanet 137 TL3 KACO blueplanaet 150 TL3
1
1