Any other use is regarded as unintended use.
This includes:
EN
Use of a distribution system that is not described (grid type)
Use of sources other than PV-strings.
Mobile use
Use in rooms where there is a risk of explosion
Use in direct sunlight, rain or a storm or in other tough environmental conditions
Outdoor use in environmental conditions that exceed the limits stated in the technical specifications >Environmental
data [See section 4.3} Page 11].
Operation outside the specifications prescribed by the manufacturer
Modifying the device
Stand-alone operation
2.2
Protection features
The following monitoring and protection functions are built-in:
Overvoltage conductor/varistor to protect the power semiconductors from high-energy transients on the grid and gen-
erator side
Device temperature monitoring system
EMC filters to protect the product from high-frequency grid interference
Grid-side grounded varistors to protect the product against burst and surge impulses
Islanding detection (anti-islanding) according to the current standards
ISO/AFI detection of a generator insulation fault.
3
Device description
3.1
Function
The device converts the DC voltage generated by the PV modules into AC voltage and feeds it into the grid. The starting
procedure begins when there is sufficient sunlight and a specific minimum voltage is present in the device. The feed-in
process begins once the PV generator has passed the insulation test and the grid parameters are within the requirements
imposed by the grid operator for a specific monitoring time. If, as it gets dark, the voltage drops below the minimum
voltage value, feed-in mode ends and the device switches off.