6.4
Making the electrical connections
NOTE
Select the cable cross-section, fuse type and fuse value in accordance with the following master condi-
tions:
Country-specific installation standards
Power class of the device
Line length
Type of line installation
Local temperatures
6.4.1 Supply line and fuse requirements
AC-side
Max. cable cross-section
Min. cable cross-section
Diameter of cable for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Electrical protection in installation (provided by the customer)
Fitting for AC connection
Torque for cable fitting
DC-side
Max. cable cross-section
Min. cable cross-section
Diameter of cable for cable fitting
Cable lug dimension b width max.
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
Interfaces
Diameter of cable for cable fitting
Torque for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Diameter of cable for cable fitting
Torque for cable fitting
Ethernet connection type
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanaet 150 TL3
240mm² (AL or CU)
acc. to local installation standards
16 - 28 mm
Depending on the ring cable lug
Bore for M10 screw
30 Nm
Cable lug
42 mm
M10
10 Nm
max. 250A
M40
7.5 Nm
240mm² (AL or CU)
acc. to local installation standards
16 - 28 mm
42 mm
Depending on the ring cable lug
Solar cable
10 mm
30 Nm
M40
7.5 Nm
(2x) 8 - 17 mm
5 Nm
spring-type terminal
0.25 - 1.5 mm²
(3x) 5 - 10 mm
2.5 Nm
RJ45
EN