LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 5335D or 5337D the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate
Marking
Standards
Hazardous area
Zone 0, 1, 2, 20, 21, 22 and Coal mining
T4: -40 ≤ Ta ≤ 85ºC
T6: -40 ≤ Ta ≤ 45ºC
Terminal: 3,4,5,6
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Revision date:
2014-03-31
16
IECEx Installation drawing 5335QI01
IECEx KEM.10.0083X
Ex ia IIC T6..T4 Ga
Ex ia IIIC Da
Ex ia I Ma
IEC60079-11:2011, IEC60079-0: 2011, IEC60079-26:2006
6
5
4
5335D
3
5337D
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
Version Revision
V4R0
WWW.PRELECTRONICS.COM
Non Hazardous Area
+
1
-
2
Barrier
Doc. No.
5335QI01 V4R0
5335V117-ES
5335QE01
Page:
1/2