III Adjustment procedure
In all input voltage ranges, the offset adjustment
is made at 0 V input voltage.
The adjustment of the offset and of the gain can
be repeated until the desired accuracy is reached.
1. Select the desired input and output signal (see table 1
and 2)
2. Adjustment of the offset:
Adjust the offset by means of potentiometer
desired lowest level of the output signal.
3. Adjustment of the gain:
Apply the desired input voltage and select the input range
by means of the front-face rotary switch
by means of the potentiometer
output signal.
Depending on the configuration of the DIP switches, the
CC-U/V provides 2 synchronously working outputs:
One output for voltage and one for current.
One of these outputs can be adjusted with the front-face
potentiometers. The other, non ajdusted, output is within a
tolerance of 2 % of the adjusted output.
English
to the
. Adjust the gain
to the desired highest
III Procédure de réglage
Dans toutes les plages de tension d'entrée, le
réglage de l'offset est fait à une tension d'entrée
de 0 V.
Le réglage de l'offset et du gain peut être répeté
jusqu'à obtention de la précision désirée.
1. Sélectionner les signaux d'entrée et de sortie désirés
(voir tableaux 1 et 2)
2. Réglage de l'offset:
Régler l'offset à l'aide du potentiomètre
minimal désiré du signal de sortie.
3. Réglage du gain:
Appliquer la tension d'entrée désirée et sélectionner la
plage d'entrée, en utilisant l'interrupteur rotatif
avant. Régler le gain, à l'aide du potentiomètre
grande valeur de sortie désirée.
Selon la configuration des micro-interrupteurs, le
CC-U/V possède 2 sorties travaillant de manière
synchrone:
Une sortie tension et une sortie courant.
Une de ces sorties peut être réglée par les potentiomètres
sur la face avant. La sortie non-réglée est dans une plage
de tolérance de 2 % par rapport à celle ajustée.
Français
sur le niveau
sur la face
, à la plus
10