Fitting and installing the pneumatic components
Mount the SPC-10 horizontally or vertically on a level surface
with the aid of the support brackets supplied. You will require at
least 3 screws (M4) here.
Compressed air / service unit
5 to 7 bar, dried, non-lubricated 5 µm filter element
Max. deviation in compressed air at the MPYE-5-... +/- 1 bar
Sufficient standard flow (reference value: twice the standard
flow of the valve)
Microfilter if slight oil mist cannot be avoided.
Proportional directional control valve (type MPYE-5-...)
This should be fitted and connected up symmetrically to the
centre of the cylinder. If fitted to moving parts, the
MPYE-5-... should be mounted at right angles to the
direction of movement.
Fit silencers with large rated flow (e.g. U-1/8), maximum
length of tubing 1 m.
Compressed air tubing and screw connectors
Lay the tubing from the valve to the cylinder symmetrically.
Tubing length = cylinder length.
Dimensions corresponding to rated size of the service unit,
the proportional directional control valve and the cylinder.
If
angled
connectors
connectors from the Quick Star series.
Do not use any restrictors in the supply tubing.
9902c
cannot
be
avoided,
use
plug
13