7.13.5 Tabla de supervisores LCP DX
Tab. 13: Tabla de supervisores LCP DX – Variables analógicas
BMS Ad-
Description
dress
1
Reserved – (not used or other special appli-
cation or internal debug)
2
B2 probe value: LCP Server IN
3
B3 probe value: LCP Server IN
4
B4 probe value: LCP Server IN
5
Reserved – (not used or other special appli-
cation or internal debug)
6
B6 probe value: ROOM Server OUT
7
B7 probe value: ROOM Server OUT
8
B8 probe value: ROOM Server OUT
9
B9 Probe value: Compressor discharge
temperature
10
B10 Probe value: Compressor suction tem-
perature
11
B11 probe value: High pressure – Compres-
sor Discharge Pressure
12
B12 probe value: Low pressure – Compres-
sor Suction Pressure
13
Evaporator temperature from Low pressure
conversion
14
Condensing temperature from High pressu-
re conversion
15...20
Reserved – (not used or other special appli-
cation or internal debug)
21
Server Medium Temp Out – (Room)
22
Server Medium Temp In – (LCP)
23...44
Reserved – (not used or other special appli-
cation or internal debug)
45
Compressor Rotor speed
46
Compressor Motor current
47
Reserved – (not used or other special appli-
cation or internal debug)
48
Main Setpoint LCP
49...207
Reserved – (not used or other special appli-
cation or internal debug)
Rittal Liquid Cooling Package
UOM
Min
Max
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
bar
-99,9
99,9
bar
-99,9
99,9
°C
-99,9
99,9
°C
-99,9
99,9
–
–
–
°C
-99,9
99,9
°C
-99,9
99,9
–
–
–
rps
0
999,9
A
0
99,9
rps
0
999,9
°C
-99,9
99,9
–
–
–
7 Manejo
Read/
Note
Write
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
–
only for Service/
Manufacturer
R
Customer
R
Customer
–
only for Service/
Manufacturer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R/W
Customer
–
only for Service/
Manufacturer
ES
37