Rittal TopTherm LCP Rack DX Instrucciones De Montaje Y Funcionamiento página 39

Tabla de contenido

Publicidad

Tab. 15: Tabla de supervisores LCP DX – Variables digitales
BMS Ad-
Description
dress
1
Reserved – (not used or other special appli-
cation or internal debug)
2
Digital input 2: Drive/Compressor Overload
3
Digital input 3: High Pressure Switch Alarm
4...7
Reserved – (not used or other special appli-
cation or internal debug)
8
Digital input 8: Remote ON/OFF
9...10
Reserved – (not used or other special appli-
cation or internal debug)
11
General Inverter Alarm
12
Power+ Drive Off–Line Alarm
13...16
Reserved – (not used or other special appli-
cation or internal debug)
17
Digital output 1: Compressor On
18...22
Reserved – (not used or other special appli-
cation or internal debug)
23
Digital output 7: General Alarm Contact
24...28
Reserved – (not used or other special appli-
cation or internal debug)
29
Command to reset all alarms by Supervisor
30
Envelope Alarm: Memory alarm compressor
forced off working out envelope
31
Compressor startup failure alarm: reach max
retry number
32
Compressor startup failure alarm used for
the alarm mask visualization
33
Memory Alarm max discharge temperature
34
Reserved – (not used or other special appli-
cation or internal debug)
35
Memory alarm Delta pressure too big to
startup compressor
36
Memory alarm control for oil return when
compressor is running (lubrication)
37
Reserved – (not used or other special appli-
cation or internal debug)
38
Memory alarm probe broken (analogic input
B2): LCP Server IN
39
Memory alarm probe broken (analogic input
B3): LCP Server IN
Rittal Liquid Cooling Package
UOM
Min
Max
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
7 Manejo
Read/
Note
Write
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
only for Service/
Manufacturer
R/W
only for Service/
Manufacturer
R
Customer
R
Customer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
ES
39

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Toptherm lcp inline dx

Tabla de contenido