English Section

ENI Port Identification

PENI Specifications

3
InView EtherNet/IP Module
(Catalog Number 2706-PENI)
InView DeviceNet Module
(Catalog Number 2706-PDNI)
Ethernet Port (ENI Port 1)
Use this write-on area to mark
the Ethernet IP address
Description
24V dc Power Source Requirement
24V dc Current Draw
Maximum Inrush Current
Internal Isolation
Operating Ambient Temperature
Storage Temperature

Installation Instructions

ETHERNET
RS232
FAULT
NET
RS-232 Mini-DIN (ENI Port 2)
TX/RX
TX/RX
IP
PWR
CABLE
EXTERNAL
Power Source Switch -
(Set to EXTERNAL)
ENI Specification
20.4 to 26.4V dc
50 mA typical, 100 mA maximum
200 mA
500V ac for one minute
0° C to +50° C (+32° F to +122° F)
-40° C to +85° C (-40° F to +185° F)