PanelView 550 Terminals

Connecting AC Power

The table below shows the electrical ratings for the AC versions of the terminals.
Terminal Type
PV550
• The PanelView 550 terminal is designed for safe use when
ATTENTION
• Do not apply power to the terminal until all wiring
Explosion Hazard - Do not connect or disconnect equipment
ATTENTION
while circuit is live unless area is known to be non-hazardous.
To connect AC power to the PanelView 550 terminals:
1. Secure the AC power wires to the L1 and L2N terminal block screws.
2. Secure the Earth Ground/Protective Earth wire to the GND screw on the
terminal block.
ATTENTION
Publication 2711-IN009D-MU-P
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Supply Voltage
Power Consumption
85 to 264V ac, 47 to 63 Hz
45 VA maximum
installed in a suitably rated NEMA Type 12, 13, 4X (indoor
use only), IP54 or IP65 enclosure.
connections have been made. Failure to do so may result
in electrical shock.
Improper wiring of the power terminals may result in
voltage at the communication connector shells. Refer to
the following figure when wiring.