The following PV550 terminals have an operating temperature code of T2
(maximum operating temperature of 300° C or 572° F).
• keypad terminals (series G or earlier)
• keypad and touch screen terminals (series G or earlier)
Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 300° C (572° F).
The following PV550 following PV550 terminals have an operating temperature
code of T4 (maximum operating temperature of 135°C or 275°F).
• keypad terminals (series H and later)
• keypad and touch screen terminals (series H and later)
Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 135°C (275°F).

European Union Directive Compliance

If a PanelView 550 Operator Terminal is installed within the European Union or
EFTA regions and has a CE mark, the following regulations apply.
EMC and Low Voltage Directives
This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic
Compatibility (EMC) and amending directives 91/263/EEC, 92/31/EEC, 93/68/EEC;
72/23/EEC Low Voltage Directive, and amending directive 93/68/EEC using the
following standards, in whole or in part:
• EN 50081-2:1993 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 61000-6-2:1999 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
• EN 61131-2:1995 EMC - Programmable Controllers - Equipment
Requirements and Tests
• Low Voltage Directive - Safety Sections of EN 61131-2
The product described is intended for use in an industrial environment.

Intended Use of Product

According to these Standards, the factor which determines, for EMC purposes,
whether an apparatus is deemed to be "Industrial" or "Residential, commercial and
light industrial", is given in Clause 1 of EN50081-2 as follows:
Apparatus covered by this standard is not intended for connection to a
public mains network but is intended to be connected to a power network
supplied from a high- or medium-voltage transformer dedicated for the
supply of an installation feeding a manufacturing or similar plant.