BTL5-H1_ _-M_ _ _ _-HC/WC-S94
Micropulse Linear Transducer - Rod Style
3
Installation (cont.)
3.3
Magnets, Installation
A magnet is required for each trans-
ducer. This must be ordered sepa-
rately ➥ ➥ ➥ ➥ ➥ Fig. 3-4.
For mounting the magnet we rec-
ommend to use non-magnetizable
material ➥ ➥ ➥ ➥ ➥ Fig. 3-2.
4
Wiring
Note the following when mak-
ing electrical connections:
System and control cabi-
net must be at the same
ground potential.
To ensure the electromagnetic
compatibility (EMC) which Balluff
warrants with the CE Mark, the
6
english
BTL-P-0814-GR-PAF
BTL-P-1013-4R
Fig. 3-4: Magnet (optional)
following instructions must be
strictly followed.
BTL transducer and the control-
ler/master must be connected
using shielded cable.
Shielding: Copper filament
braided, 85% coverage.
BTL-P-1014-2R
BTL-P-1013-4S
BTL-P-1012-4R
The shield should be grounded
only at the control side in order
to avoid potential compensation
– current flow – over the shield.
Pin assignments can be found in
➥ ➥ ➥ ➥ ➥ Table 4-2.