2.2. REAR PANEL
1. 24 Vdc Power Input.
24 Vdc input for sealed lead‐acid battery, UPS or equivalent product.
2. 6 x AB speaker outputs.
100 V line speaker outputs.
3. 6 x 24 Vdc attenuator output interface.
6 output to be used for 4 wire attenuator system. All 6 are activated during emergency or
paging operations. Maximum 0.2 A per contact. Total maximum power 28 W.
4. 8 x General Control Outputs.
Multifunctional relay output contacts programed by software.
5. 8 x General Control Inputs.
Multifunctional control inputs programed by software.
NOVA Version 1.0
NOVA
Voice Evacuation System
Page 7 of 34