P0010
1 = Çabuk
devreye alma
P0100
0 = kW / 50 Hz
1 = hp / 60 Hz
2 = kW / 60 Hz
P0304*)
10 V – 2000 V
P0305*)
0 ... 2 * I nom
P0307*
0 kW– 2000 kW
P0310*
12 – 650 Hz
10
PDF created with pdfFactory Pro trial version
English
Start Quick Commissioning
P0010 must always be set back to '0'
before operating the motor. However if
P3900 = 1 is set after commissioning
this is done automatically
Operation for Europe / N. America
for setting 0 and 1 use DipSwitch 2.
For setting 2 use P0100.
Rated Motor Voltage
Nominal motor voltage (V) from rating
plate
Rated Motor Current
Nominal motor current (A) from rating
plate
Rated Motor Power
Nominal motor power (kW) from rating
plate. If P0100 = 1, values will be in hp
Rated Motor Frequency
Nominal motor frequency (Hz) from
rating plate
Deutsch
Start Schnellinbetriebnahme
P0010 muss vor der Inbetriebnahme des
Motors auf '0' zurückgesetzt werden. Wird
nach der Inbetriebnahme P3900 = 1
eingestellt, dann erfolgt dies automatisch.
Betrieb für Europa / Nordamerika
Die Einstellungen 0 und 1 sind über Dip
Switch 2 herzus tellen.
Einstellung 2 über P0100
Motorbemessungsspannung
Motorbemessungsspannung (V) vom
Typenschild des Motors
Motornennstrom
I nom = Motornennstrom (A) aus dem
Typenschild
Motornennleistung
Motornennleistung (kW) aus dem Typen-
schild. Bei P0100 = 1, sind die Werte in hp
Motornennfrequenz
Motornennfrequenz (Hz) aus dem
Typenschild