Connecting the FCS-320-TM series

Figure 3, Page 4
Designation
V+
V-
L+
L -
L+
L -
Reset+
Reset-
V+
V-
L+
L -
L+
L -
Data+
Data-

Configuration

The detector and detection device are configured once the aspirating smoke detector has
been connected to the fire panel.
The aspirating smoke detectors in the FCS-320-TM series are preconfigured at the factory.
Check whether this configuration is suited to the local conditions. Perform object-specific
configuration adjustments using the FAS-ASD-DIAG Diagnostic Software.
Sensitivity
Delay
Activation threshold of the airflow monitoring
Delay time of the airflow malfunction
Pre-alarm threshold
Fault indication
Dynamic air flow
ROOM·IDENT
LOGIC·SENS
Main alarm after ROOM·IDENT
Fan voltage

Settings via the FAS-ASD-DIAG Diagnostic Software

The settings described below only refer to the FCS-320-TM-R device variants.
Fire source identification
NOTICE!
The term "ROOM·IDENT" is used in the FAS-ASD-DIAG Diagnostic Software for the
identification of the fire source.
Fire source identification is activated/deactivated using the FAS-ASD-DIAG Diagnostic
Software via the "Settings" screen. The "ROOM·IDENT" function is deactivated as standard.
Main Alarm following Fire Source Identification
For certain applications, it is practical to perform the alarm signaling once the fire location
has been identified. To do this, the "Fire alarm after ROOM·IDENT" must be activated. It is
important to remember that when this function is activated, the "ROOM·IDENT" function must
F.01U.123.590 | 1.0 | 2009.11
Terminal
Function
1a
Power supply, incoming
2a
3a
Alarm zone, incoming
4a
5a
Tamper zone, incoming
6a
7a
Data line connection for digital remote indicator*
8a
1b
Power supply, outgoing
2b
3b
Alarm zone, outgoing
4b
5b
Tamper zone, outgoing
6b
7b
Indicator bus
8b
FCS-320-TM | FCS-320-TM-R
Default value
0.5 %/m
10 s
20%
100 s
60%
off
off
off
on
off
9 V
Bosch Sicherheitssysteme GmbH