GATE DELAY DURING CLOSING
In order to avoid the colliding of gate's during the closing the
time of delay should de introduced r.Ch, which is adjustable
from 0 to 2 minutes. In such a case the closing time of
gate1 is delayed in comparison to the gate2.
LOCK TIME
Before the opening phase starts, the gearcase has to energi-
ze the electrical lock in order to release it and enable the
gate movement. The time t.SEr determines the duration of
excitation, and is adjustable from 0 to 3 seconds. In case
there is no motor lock, set up on no.
BACKLASH TIME
To help release the electric lock it is possible to set an
inversion time, ranging from 0 to 3 seconds.
During inversion time motors are driven in the closing direc-
tion while lock is operated. If you set an inversion time grea-
ter than lock time, motors are driven in the closing direction
only while the lock time lasts.
PRE-FLASHING TIME
This menu permits the introduction of a pre-flashing that
occurs before any movement of the gate either in opening or
in closing phase: the time of pre-flashing can be adjusted
from 0 to 2 minutes.
MOTOR 1 POWER
Such a menu enables the sensitivity adjusting of the motor 1
current sensor from 1A to 7A.
MOTOR 2 POWER
Such a menu enables the sensitivity adjusting of the motor 1
current sensor from 1A to 7A.
START SLOWING DOWN
Such a menu enables the motor slowing down start as for
the opening and closing phase.
END OF STROKE SLOWING DOWN
Such a menu allows enabling the door slowing down at their
end of stroke by means of two speeds which can be set up
according to your needs.
vEL1
corresponds to 25% of power.
vEL2
corresponds to 50% of power.