1. Introduction
ACTION 09 is a control unit suitable to the control of sectional doors moved by 24Vcc motors with encoder. The coexistence of several types of
safeties, such as, for example the control of the current absorbed by the motor and the velocity control, allows a rapid intervention on the anti –
squashing prevention. The particular technology utilized allows the learning and the dynamic adjusting of the efforts required to the motor in the normal
functioning. The handling of the position by encoder installed in the motor, allows the use in absence of electric limit switches.
ACTION 09 has inputs dedicated to the limit switches connection, step by step connection, pedestrian button, clock, photo – devices and safety stop,
further the output for flashing light 24Vac.The control unit allows the adjusting by trimmer of the automatic reclosing time and of the force exercised by
the motor.
2. Configuration
Use this point to connect
the motor's casing to the
control unit and to the
ground.
Little bridges (if present)
to invert the motor's
phase.
Connect the battery
charger card
3. Electrical connections
Terminal
1 – 2
Flashing light output
3
Positive power supply TX & RX photocell
4
Negative power supply TX photocell
5
Negative power supply RX photocell and
common button and safety
6
Closing limit switches
7
Opening limit switches
8
STOP button input
9
RX photocell contact input
10
Pedestrian button input
11
Step by step button input
12
Antenna screen input
13
Antenna input
IMPORTANT: to obtain a correct working of the accessories (photo devices in particular) connected to the control box, is very important that the
entire system (motor+ control box) has a single mass reference system. You must therefore connect a small cable between the motor casing and the
control box at the point shown in the figure. If there is a good ground connection it is advisable to connect it to the system.
6-1622356 rev.4 09-07-2013
WARNING: the control unit ACTION 09 must be used with
transformers TCT50 (230Vac) or TCT34 (120vac)
A B C D E
Function
OUT: 24 Vac 25 W MAX
Normally closed (NC)
Normally closed (NC)
Normally closed (NC)
Normally closed (NC)
Normally open (NO)
Normally open (NO)
Any contact which is
Normally Closed (N.C.)
Must be bridged to the
common if not used.
ITA
Automatic
reclosing
Connector motor/encoder
Setting
OUT: +24Vcc
OUT: GND TX
OUT: GND RX
Common
Photocells
Power supply
GND
Antenna
5
6
7
8
9 10
Note: Correspondance colours valid only for PRAKT motor.
ENG
FRA
ESP
DEU
POR
Connector Motor/ Encoder
A
B
C
D
E
Setting maximum
threshold torque
Radio module
Buttons:
1= yellow
2= blue
3= red
Manual ( Left) / automatic
( right) operation selector .
Encoder +5Vcc (brown)
Signal (green)
GND (white)
Motor
pag. 2 di 8